Three models supporting 10 safety component inputs and 4 semiconductor safety outputs at most can be selected. Configuration software can be used to conveniently set safety control logic for meeting various on-site application needs.
Having authoritative CE and TUV certifications, and reliable performance meeting the requirements of Cat.4, PLe (based on ISO13849) or SIL3 (based on IEC62061)
The logical relationship between all safe inputs and outputs can be directly programmed and associated through the software interface. Different levels of delay outputs can be set and up to 18 logical function blocks can be associated
A single product can help to provide 6 dual-channel safety contact inputs, 2 relay contact safety signal outputs and 4 semiconductor outputs
When 6 sets of safety contacts are input simultaneously for a single machine, the product width is only 45mm, saving space and facilitating wiring
Model
|
SR-P3-2O | SR-P6-2O4S |
Order No
|
693100002 | 693100003 |
Standard
|
Safety integrity level: SIL3
Performance level: PLe
Safety category: Cat. 4
|
|
Input channel
|
3 | 6 |
Input current
|
≤50mA(24V DC) | |
Lead resistance
|
≤15Ω | |
Input device
|
Emergency stop button, Safety door switch, safety light curtain,
safety mat, two-hand control button, door magnetic switch and reset button
|
|
Number of contacts
|
2NO | 2NO,4SO |
Contact material
|
AgSnO₂ | |
Contact fuse protection
|
10A Fast ;6A Slow | |
Switching capacity
|
5A/250V AC;5A/24V DC | |
Supply voltage
|
24V ~30V DC | |
Current loss
|
≤100mA(24V DC) | |
Suction buffer time
|
≤100ms | |
Release / buffer time
|
≤30ms | |
Recovery time
|
≤100ms | |
Short time power interruption
|
20ms | |
Electromagnetic compatibility
|
EN60947,EN61000-6-2,EN61000-6-4 | |
Vibration frequency
|
10HZ~55HZ | |
Vibration amplitude
|
0.35mm | |
Operating temperature
|
-20℃~+60℃ | |
Storage temperature
|
-40℃~+85℃ | |
Relative humidity
|
10%~90% | |
Overvoltage level
|
III | |
Contamination level
|
2 | |
Rated insulation voltage
|
250V AC | |
Rated impulse voltage
|
6000V(1.2/50us) | |
Insulating strength
|
1500V AC,1min | |
Electrical clearance and creepage distance
|
Meeting EN60947-1 |
Model | SR-P10-4S |
Order No | 693100004 |
Standard
|
Safety integrity level: SIL3
Performance level: PLe
Safety category: Cat. 3
|
Input channel
|
10 |
Input current
|
≤10mA(24V DC) |
Lead resistance
|
≤15Ω |
Input device
|
Emergency stop button, Safety door switch, safety light curtain, safety mat, two-hand control button, door magnetic switch, reset button and heartbeat sensor
|
Control logic
|
10 types, new logic is customizable depending on customer requirements
|
Delay setting time
|
0s~99s |
Heartbeat monitoring frequency
|
0.1Hz ~10Hz |
Frequency output logic block
|
0.1Hz ~10Hz |
Output quantity
|
4SO |
Drive capability
|
2A(24V DC) |
Suction buffer time
|
≤100ms |
Release / buffer time
|
≤30ms |
Recovery time
|
≤100ms |
Short time power interruption
|
20ms |
Supply voltage
|
24V ~30V DC |
Current loss
|
≤100mA(24V DC) |
Electromagnetic compatibility
|
EN60947,EN61000-6-2,EN61000-6-4 |
Vibration frequency
|
10HZ~55HZ |
Vibration amplitude
|
0.35mm |
Operating temperature
|
-20℃~+60℃ |
Storage temperature
|
-40℃~+85℃ |
Relative humidity
|
10%~90% |
Overvoltage level
|
III |
Contamination level
|
2 |
Rated insulation voltage
|
250V AC |
Insulating strength
|
1500V AC,1min |
Electrical clearance and creepage distance
|
Meeting EN60947-1 |